Maintenance
NOTE: Before removing the detector, notify the proper
authorities that the smoke detector system is
undergoing maintenance and will temporarily be
out of service. Disable the zone or system under-
going maintenance to prevent unwanted alarms.
Figure 5. Removal of cover and screen for cleaning:
REMOVABLE
SCREEN/COVER
(PART NO.
C58-357-XX)
1. Remove cover by turning counter-clockwise in the direc-
tion of arrow.
2. Vacuum the cover carefully.
3. Remove the sensing chamber cover (See Figure 5).
4. Clean the sensing chamber by vacuuming or blowing
out dust and particles.
5. Replace the sensing chamber cover, aligning the arrow
on the top of the chamber cover with the arrow on the
housing.
6. Replace the cover by placing it over the sensing cham
ber cover and twisting until it snaps into place.
7. Reinstall the detector.
8. Notify the proper authorities the system is back in operation.
SENSING
CHAMBER
COVER
HOUSING
A78-2565-07
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
System Sensor warrants its enclosed smoke detector to be free from Please include a note describing the malfunction and suspected cause of
defects in materials and workmanship under normal use and service for a failure. The Company shall not be obligated to repair or replace units
period of three years from date of manufacture. System Sensor makes no which are found to be defective because of damage, unreasonable use,
other express warranty for this smoke detector. No agent, representative, modifications, or alterations occurring after the date of manufacture. In no
dealer, or employee of the Company has the authority to increase or alter case shall the Company be liable for any consequential or incidental dam-
the obligations or limitations of this Warranty. The Company’s obligation ages for breach of this or any other Warranty, expressed or implied what-
of this Warranty shall be limited to the repair or replacement of any part soever, even if the loss or damage is caused by the Company’s negligence
of the smoke detector which is found to be defective in materials or work- or fault. Some states do not allow the exclusion or limitation of incidental
manship under normal use and service during the three year period com- or consequential damages, so the above limitation or exclusion may not
mencing with the date of manufacture. After phoning System Sensor’s toll apply to you. This Warranty gives you specific legal rights, and you may
free number 800-SENSOR2 (736-7672) for a Return Authorization number, also have other rights which vary from state to state.
send defective units postage prepaid to: System Sensor, Repair
D200-54-00
4
I56-710-14R