Examples (0-5V Inputs)
1. Desired display readings are:
ON
0.0V input = "0.00"
5.0V input = "6.00"
12345678
Use DIP-switch setting #3 in Table 1 and enable decimal point DP2
via SW7. Apply 0.0V and adjust R3 so the display reads "0.00".
Apply 5.0V and adjust R7 so the display reads "6.00".
2. Desired display readings are:
ON
0.0V input = "000"
5.0V input = "800"
12345678
Use DIP-switch setting #2 in Table 1. Apply 0.0V and adjust R3 so
the display reads "000". Apply 5.0V and adjust R7 so the display
reads "800". For these display readings, no decimal points are
used. Set SW6, SW7 and SW8 to OFF.
3. Desired display readings are:
ON
0.0V input = ".000"
5.0V input = ".250"
12345678
Use DIP-switch setting #5 in Table 1 and enable decimal point DP1
via SW6. Apply 0.0V and adjust R3 so the display reads "000". Apply
5.0V and adjust R7 so the display reads ".250".
Table 1. 0-5V DIP-Switch Settings €
Display Reading
SW1 SW2 SW3 SW4
0.0V Input
1. 000
2. 000
3. 000
4. 000
5. 000
6. 000
7. 000
8. 000
5.0V Input
1200-1999
700-1200
400-700
300-400
190-300
120-190
100-150
90-140
Off
Off Off Off
On
Off Off Off
Off
On Off Off
Off
Off On Off
Off
On On Off
Off
Off On On
Off
On On On
On
On On On
Ā€ The DMS-20PC-0/5 is optimized for handling 5V signal ranges that are
positioned between –0.1V and +6.0V. As such, input ranges can be anywhere
between –0.1V to +4.9V and +1.0V to +6.0V as long as their full range is
5 Volts. The meter's zero/offset potentiometer (R3) has enough adjustment
range to produce a "000" display reading for input signal levels between
– 0.1V and +1.0V.
Please note the DMS-20PC digital panel meter from which the DMS-20PC-0/5
is derived has an accuracy specification of ±2 counts (max.). Thus, it may not
always be possible to obtain the exact desired display readings.
DMS-20PC-0/5 Series
0-5V and 0-10V Input 3½ Digit, LED
Display Process Control Monitors
4. Desired display readings are:
ON
1.0V input = "000"
6.0V input = "090"
12345678
Even though this input is positioned between +1.0V and +6.0V,
it still meets the 5V full scale input range listed in the Functional
Specifications section. Use DIP-switch setting #8 in Table 1. Apply
1.0V and adjust R3 so the display reads "000". Apply 6.0V and adjust
R7 so the display reads "090". With this type of input, it is advisable
to recheck both input levels to be sure the potentiometer settings do
not affect one another.
0-10V Inputs
While the DMS-20PC-0/5 is optimized for operation with 0-5V inputs,
its versatile input stage can also accommodate most 0-10V applica-
tions. The meter's zero/offset potentiometer (R3) has enough adjust-
ment range to produce a "000" display reading with input signal levels
between –0.1V and +1.0V. Table 2. summarizes the available ranges
when the DMS-20PC-0/5 is used with 0-10V inputs.
Example (0-10V Inputs)
1. Desired display readings are:
ON
0.0V input = "000"
10.0V input = "500"
12345678
Use DIP switch setting #4 in Table 2. Apply 0.0V and adjust R3 so
the display reads "000". Apply 10.0V and adjust R7 so the display
reads "500".
Table 2. 0-10V DIP-Switch Settings
Display Reading
SW1
0.0V Input 10.0V Input
1. 000
1400-1999
On
2. 000
800-1400
Off
3. 000
600-800
Off
4. 000
380-600
Off
5. 000
240-380
Off
6. 000
200-300
Off
7. 000
180-280
On
SW2 SW3 SW4
Off Off Off
On Off Off
Off On Off
On On Off
Off On On
On On On
On On On
www.murata-ps.com
Technical enquiries email: sales@murata-ps.com, tel: +1 508 339 3000