Qdatasheet_Logo
Integrated circuits, Transistor, Semiconductors Search and Datasheet PDF Download Site

DMS-20PC-4/20B View Datasheet(PDF) - DATEL Data Acquisition products

Part Name
Description
MFG CO.
DMS-20PC-4/20B
Datel
DATEL Data Acquisition products  Datel
'DMS-20PC-4/20B' PDF : 5 Pages View PDF
1 2 3 4 5
3½ D I G I T, L E D D I S P L AY, 4 - 2 0 m A L O O P - P OW E R E D M E T E R S
DMS-20PC-4/20
DMS20PC4/20B (Bipolar Reading Model)
The DMS-20PC-4/20B's zero-offset circuit differs from the unipolar 'S' model
described above in that with the 'B' model, a half-scale 12mA input is
normally set to display "000". Therefore, all of the of the DIP-switch settings
in Table 2 assume a reading of "000" is desired with a 12mA input. Display
readings other than those shown in Table 2 are possible, contact DATEL
for more information.
When conguring the DMS-20PC-4/20B for the rst time, or when selecting
a new range, set both R3 and R7 fully clockwise (roughly 22 turns) to
their minimum offset/minimum-span positions, respectively. Then select the
desired readings from Table 2 and congure DIP-switches SW1, SW2, and
SW3 accordingly.
The procedure below illustrates how to calibrate the DMS-20PC-4/20B to its
factory-calibrated readings of "1000" with a 4mA input and "1000" with a
20mA input. When performing DIP-switch settings, be sure the DIP-switch's
small actuators are rmly engaged in their fully-ON or fully-OFF positions.
1. Set both R3 and R7 fully clockwise.
2. Select DIP-switch setting #1 from Table 2.
3. Apply a precision 12mA input and adjust R3 until the meter's display
reads "000".
4. Apply a precision 20mA input and adjust R7 until the meter's display
reads "1000".
5. Apply a precision 4mA input and the display should read "1000".
Repeat steps 3 and 4 to make sure the two adjustments did not
affect one another.
Table 2. DMS-20PC-4/20B (Bipolar Model) DIP-Switch Settings
Display Reading
SW1 SW2 SW3
4mA
12mA 20mA
1. 600 to 1000 000 600 to 1000 Off
2. 350 to 650 000
350 to 650
On
3. 250 to 400 000
250 to 400
Off
4. 150 to 250 000
150 to 250
Off
5. 100 to 150 000
100 to 150
On
Off
Off
Off
Off
On
Off
Off
On
On
On
Examples (DMS-20PC-4/20B-Bipolar Model)
1. Desired display readings are:
ON
4mA = "1.00"
20mA = "1.00"
1 2 34 56
Use DIP-switch setting #5 in Table 2 and enable decimal point DP2 via
SW5. Apply 12mA and adjust R3 so the display reads "0.00". Apply
20mA and adjust R7 so the display reads "1.00". Apply 4mA and verify
that the display reads "1.00", readjust R3 and R7 if necessary.
2. Desired display readings are:
ON
4mA = "450"
20mA = "450"
1 2 34 56
Use DIP-switch setting #2 in Table 2. Apply 12mA and adjust R3 so
the display reads "000". Apply 20mA and adjust R7 so the display
reads "450". Apply 4mA and verify that the display reads "450".
Repeat adjustment procedure if necessary. For these display readings,
no decimal points are used. Set SW4, SW5 and SW6 to OFF.
3. Desired display readings are:
ON
4mA = "650"
20mA = "650"
1 2 34 56
Notice that these readings can be obtained using either DIP-switch
setting #1 or DIP-switch setting #2 in Table 2. In situations like this
where DIP-switch settings overlap, less-sensitive R3/R7 adjustments
can be achieved if the higher DIP-setting # is selected (setting #2 in
this example). Apply 12mA and adjust R3 so the display reads "000".
Apply 20mA and adjust R7 so the display reads "650". Apply 4mA and
verify that the display reads "650". Repeat adjustment procedure if
necessary.
DMS-20PC-4/20P (Positive Reading Model)
The DMS-20PC-4/20Ps Zero-Offset circuit is optimized to produce positive
readings at both 4mA and 20mA input levels. As shown in Table 3s rst
three columns, a 4mA input can be typically adjusted (using R3, Zero/Offset
Adjust) to display any positive reading between 000and 800. The cor-
responding 20mA-input reading is then added to the 4mA offset as a
differential whose magnitude is varied by adjusting R7 (Gain/Span Adjust).
The Differential Rangecolumn in Table 3 lists the nominal differential
display-readings which can be obtained with R7 at, or very close to, its
full-clockwise, minimum span position. The Differential Range column can
be used as a guide when conguring the meter for the majority of user
applications. Higher differential ranges are obtainable; however, the use
of higher differential readings results in correspondingly-lower positive read-
ings with 4mA inputs, that is, R3s clockwise adjustment-range is reduced.
Example #3 below illustrates this concept. Please contact DATEL if there is
any doubt as to whether or not the DMS-20PC-4/20P can be congured for
your display readings requirements.
The rst step when conguring the DMS-20PC-4/20P for the rst time, or
when selecting a new range, is to set R3 fully counterclockwise and R7
fully clockwise (roughly 22 turns) to their minimum offset/minimum span
positions, respectively.
The next step is to calculate the required display differential-reading; this
is accomplished by subtracting the desired 4mA display reading from the
desired 20mA display reading, disregarding decimal points. Then, using
the calculated differential display-reading to select the appropriate DIP-
switch setting # from Table 3, congure DIP-switches SW1, SW2, and SW3
accordingly. Make certain that the DIP-switchs small actuators are rmly
engaged in their fully-ON or fully-OFF positions.
The procedure below describes how to calibrate the meter for an appli-
cation which the DMS-20PC-4/20P easily accommodates: displaying the
output of a 4-20mA transmitter, that is, 04.0with a 4mA input and 20.0
with a 20mA input.
DATEL, Inc., Manseld, MA 02048 (USA) Tel: (508)339-3000, (800)233-2765 Fax: (508)339-6356 Email: sales@datel.com Internet: www.datel.com
3
Share Link: GO URL

All Rights Reserved © qdatasheet.com  [ Privacy Policy ] [ Contact Us ]