Description
The Gamewell-FCI Velociti® Series, addressable monitor module AMM-2F is a single Style B, Class B initiating device circuit (IDC) with a 47KW end-of-line resistor. This module provides an address for any device or group of devices connected to this circuit on the signaling line circuit (SLC) of the Gamewell-FCI addressable series fire alarm control panel. Any initiating device with normally open (N.O.) dry contacts may be made addressable when connected to the AMM-2F module.
FEATUREs
• Compact size allows easy installation
• Class B, Style B, initiating circuit
• 40 Ohm line resistance for each initiating device
circuit
• Connects to any normally open dry contact device
• Bicolor LEDs flash green whenever the module
is addressed, and light steady red on alarm*
*Note: Only the red LED is operative in panels that do not
operate in Velociti® mode.